EverFocus EFC306 Manual de usuario Pagina 35

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 160
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 34
NAV IP Access controller
26
4StartingUptheController
4.1 ConnectingtoPower
YoucanpowertheNAVcontrollerbyconnectingthepowersourcetoPin13and14onthe
terminalblockonthemainmodule.
Figure31
ThevoltagerangeoftheNAVcontrollerisbetweenDC11Vand16V.Themaximum
currentis500mA.Ifthebackupbatteryisconnectedtothecontroller,apowersupplywith
DC15Visrequired.ThepowersupplyintheenclosureisDC15V.Inaddition,the
controllerprovidesa12Vpowersupplyforthereaders.Itshouldbenotedthatifa
controllerpowersmultiplereaders,thecurrentdrawwillbeincreased.Thetotalcurrent
drawcanbecalculatedasbelow:
Current(controller)=500+Current(reader)xNumberofReaders
ImportantTips:
1. Thevoltagesupplyshouldbelocatednomorethan2metersfromthecontroller.
2. Theelectriclocksandalarmdevicesmustbepoweredseparately.Thecontroller’s
powersupplycanpowerthecontrollerwiththemountedmodulesandthereaders
only,butnotthelockinghardwarenorthealarmdevices.
4.2 RestoringtheController
Torestorethecontrollertothefactorydefaultsettings,switchthepoweronwhileholding
theResetbuttononthemainmodule.
Chapter
4
Vista de pagina 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 159 160

Comentarios a estos manuales

Sin comentarios